Basic technical information of pressure transmitter
Nominal pressure range | ± 2,5kPa to 40MPa |
---|
Overpressure to 40kPa over 60 kPa to 40MPa . | 100 kPa 200 % nominal range max. 60MPa |
---|
Error | max. 1% (0.5%) |
---|
Zero temperature error | typ. 0,2% max. 0,3 %/10°C |
---|
Span temperature error | typ. 0,2% max. 0,3 %/10°C |
---|
Compensated temp. range | 20 ÷ +70°C |
---|
Operating temp. range | -15 ÷ +60°C (non condensing) |
---|
Storage temperature | -25 ÷ 100°C |
---|
Supply voltage | 10 ÷ 24V dc |
---|
Supplu current – output H | < 4mA |
---|
Output | 4 ÷ 20mA two-wire 0,2 ÷ 1mA three-wire |
---|
Operating position | arbitrary |
---|
Voltage strength | min. 1000V dc. |
---|
Protection | min. IP 54 |
---|
Hmotnost | cca 270g |
---|
Common-mode pressure for differential version | max. 1Mpa |
---|
I M1 Ex ia I Ma
II1G Ex ia IIB T4 Ga
II 1D Ex ia IIIC T135°C Da
At the customer´s wish it is possible to secure a metrological verification of the transmitters at an accredited Calibration Service Centre.
Instructions for use
- Before the transmitter is connected to the pressure circuit it is necessary to check whether the measured pressure corresponds with the nominal range of the transmitter. Even a short-time overload over the maximum permissible overpressure can cause destruction of the measuring membrane. With the differential transmitter, the user must make sure that the transmitter is not one-sidedly overloaded by pressure higher than the permitted non-destructive pressure for the nominal range!
- Especially while using a silicon membrane, it is necessary to check the resistance of materials, see the front page of this sheet. Contact the producer in case of any opacity.
- For the transmitter sealing it is recommended to use “O” ring 12x2, supplied with the transmitter. While sealing to the thread (Teflon, tow) for liquid media, it is necessary to pay high attention to caution because screwing into closed volume of liquid can cause increase of pressure and destruction of the membrane!