  • very high sensitivity

  • overpressure endurance

  • users SW configuration

  • analogue, digital and two-state outputs

  • protection IP65

  • wide temperature range

  • display fit-out possibility

SP - intelligent low pressure transmitter

Basic technical information of pressure transmitter

Nominal pressure range± 50 Pa to -100÷1000kPa
Overpressure to 2kPa
from 2kPa to 20 kPa
from 20kPa to 100 kPa
over 100 kPa
20 kPa
50 kPa
300 % nominal range
200 % nominal range
Common mode pressure for differential type10x Pdif, max. 300kPa
Sampling frequency2,5Hz (50Hz)
Errormax. 1% ± 2Pa (0,5%)
Zero temperature errortyp. 0,1%
max. 0,2 %/10°C
Span temperature errortyp. 0,1%
max. 0,2 %/10°C
Operating temperature range
with display
.
-20 ÷ +85°C
-20 ÷ +70°C
(non condensing)
Storage temperature
with display
-25 ÷ 100°C
-25 ÷ 80°C
Supply voltage5 ÷ 36V dc
Supply currenttyp. 4mA
Output4 ÷ 20mA two-wire
0 ÷ 20mA three-wire
0 ÷ 10V three-wire
0 ÷ 3V three-wire
RS232 four-wire
RS485 four-wire
USB four-wire
open collector three-wire
relay four-wire
Operating positionarbitrary
Protectionmin. IP 65
Voltage endurancemin. 1000V dc
Weightcca 250g

ČSN EN 61326-1

Instructions for use

  • Before connection of the transducer into the pressure circuit, it is necessary to verify that the pressure being measured corresponds to the nominal range of this transducer. Even a transient loading over the maximum allowable overpressure may cause a destruction of the measuring membrane!
  • If you measure a pressure of aggressive media it is necessary to verify the transducer material compatibility.
  • Caution when sealing of thread (with teflon or with oakum) in liquid medium, because of screwing into the closed volume of liquid can cause uncontrollable rise of pressure and destroy this way measuring membranes!
  • All S series transmitters are involved in the electrical circuit by the usual manner. Supply voltage is in range 5 to 36V. Especially in 2-wire connection is necessary to have this voltage at the terminals of the sensor, not for supplying whole loop.
  • In case that any of screw terminal inputs is empty, it is not possible to connect it somewhere else. Because it is electrically connected with transmitter circuits and wrong connection can result in error, non-functionality or destruction of transmitter. Specification of individual signals is on label.
  • All analog and digital circuits of transmitter are galvanically connected to shared ground, node -Ucc. At the combination of analog and digital inputs is necessary to think about it.
  • All inputs are separated by 22uH inductors and protected by varistors against short high-voltage spikes.
  • Numbering of leads corresponds to numbering of internal screw terminal.
  • Pin 6 is connected to the metal box and serves as a shielding around the sensor. Pin is galvanically isolated from electrical circuits of sensor, tested by the 1000V DC.
  • For screw terminal is allowed to use only wires with cross section max 1mm2. In case of connection more inputs and outputs we recommend to use wires with smaller cross section.

Diagram

Diagram

Transmitters are connected into electrical circuit by common way. They are protected against supply reversing polarity by series diode. ATTENTION with more-wire connection, when for example changing output and supply wire may cause transmitter damage.
Detailed description all types of electrical connections, pin assignments and protocol description for series communication are in special document, which is a part of transmitter delivery.

Pin assignments

Outputs table, pin assignments of screw terminal and connector

Conector321      
Screw terminal12345678910
4 ÷ 20mA+Ucc-Ucc   case    
0÷20mA+Ucc-UccOut  case    
0÷10V+Ucc-UccOut  case    
0÷3V+Ucc-UccOut  case    
RS232+Ucc-Ucc RxDTxDcase    
RS485+Ucc-Ucc BAcase    
Switching outputs      Re1Re2OK1OK2

Dimensions of pressure transmitter

Dimensions of pressure transmitter