Searching: SRA613A2U
Nominal pressure range | ± 10 kPa to 3MPa |
---|---|
Overpressure | 200 % nominal range (max. 4MPa) |
Sampling frequency | 2,5Hz (50Hz) |
Error | max. 0,5% |
Zero temperature error | typ. 0,1% max. 0,2 %/10°C |
Span temperature error | typ. 0,1% max. 0,2 %/10°C |
Operating temperature error with display . | -20 ÷ +85°C -20 ÷ +70°C (non condensing) |
Media temperature | -20 ÷ 100°C |
Storage temperature with display | -25 ÷ 100°C -25 ÷ 80°C |
Supply voltage | 5 ÷ 36V dc |
Supply current | typ. 4mA |
Output | 4 ÷ 20mA two-wire 0 ÷ 20mA three-wire 0 ÷ 10V three-wire 0 ÷ 3V three-wire RS232 four-wire RS485 four-wire USB four-wire open collector three-wire relay four-wire |
Operating position | arbitrary |
Protection | min. IP 65 |
Voltage endurance | min. 1000V ss |
Weight | cca 300g |
ČSN EN 61326-1
Based on customer request we can provide measurement of accredited test sensors centre and calibration services.
Transmitters are connected into electrical circuit by common way. They are protected against supply reversing polarity by series diode. ATTENTION with more-wire connection, when for example changing output and supply wire may cause transmitter damage.
Detailed description all types of electrical connections, pin assignments and protocol description for series communication are in special document, which is a part of transmitter delivery.
Conector | 3 | 2 | 1 | |||||||
---|---|---|---|---|---|---|---|---|---|---|
Screw terminal | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 |
4 ÷ 20mA | +Ucc | -Ucc | case | |||||||
0÷20mA | +Ucc | -Ucc | Out | case | ||||||
0÷10V | +Ucc | -Ucc | Out | case | ||||||
0÷3V | +Ucc | -Ucc | Out | case | ||||||
RS232 | +Ucc | -Ucc | RxD | TxD | case | |||||
RS485 | +Ucc | -Ucc | B | A | case | |||||
Switching outputs | Re1 | Re2 | OK1 | OK2 |